Induction modular boiler

It is advisable to use induction modular boiler "OASIS" of high heat rating for heating buildings with large heat volume or entire residential areas. More capacity can be provided by installation of several induction heaters. The best option is to install a heating unit in the complex with its own lighting and heating.

Induction modular boiler "OASIS" can be installed either close to the heated building or on its roof. The induction electric heaters plant manufactures induction modular boiler in modular construction, which allows to arrange the induction heating equipment and heat snap in order to comply with individual needs.

Induction modular boiler "OASIS" is a transportable thermally insulated container with lighting and temperature maintenance. Inside the box there are the induction heaters with all the necessary thermal equipment. Induction modular boiler can be used permanently, and temporary, for example, during the removal of accidents in the central heating systems. It is advisable to use induction modular boilers as a standby heating source.

 

TYPES AND SPECIFICATIONS 

 

OASIS -100

OASIS -150

OASIS -200

OASIS -250

OASIS -300

OASIS -500

OASIS -750

Number of heaters

2х50

3х50

2х100

1х250

 3х100

  2х250

  3х250

Power, kW

100

150

200

250

300

500

750

Heat power, kcal/h

84260

126390

168520

210660

252900

421400

632100

power factor

0,98

0,98

0,98

0,98

0,98

0,98

0,98

Rated current consumption of the heater, А

3х150

3х232,5

3х310

3х387

3х465

3х774

3х1161

Rated current consumption for own module needs, no more than А

3х20

3х20

3х20

3х50

3х50

3х50

3х50

Features of installed pumps (pressure/flow), m.v.st./m3/h

6,7/3.4

9.5/5.1

9.7/6.7

9.8/8.4

12/10.1

18/16.8

18/25.3

Ø outlet connections

DN 50

DN 50

DN 50

DN 65

DN 65

DN 80

DN 100

Dimensions of the modules BxLxH

3240х

4240х

2600

3240х

4240х

2600

3240х

4240х

2600

3240х

4240х

2600

3240х

4240х

2600

3240х

4240х

2600

3240х

4240х

2600

 

Dimensions, power, assembly, hydraulic and electrical circuits of the induction modular boiler "OASIS" are determined by the customer's requirement specification.